CMRR: 150 dB

NMRR: 100 dB

Drift: Zero: ±0.5 μV/°C, Span: ±20 μV/°C

Width: 72 mm

Height: 35 mm

Length: 123 mm

Memory: EEPROM: 16KB

Mounting: DIN-Rail or Wall Mount

Software: Built in: OME-WISE Firmware

Isolation: 2500 Vdc, 2-Way

Input Type: RTD

Configuration: 16-bit, SRAM: 512 KB, Flash Memory: 512KB

Output Signal: N/A

Data Interface: Ethernet

LED Indicators: PoE Power: PoE on, L1: System running, L2: Ethernet link/act, L3: Ethernet 10/100M speed

Supply Voltage: 12 to 48 Vdc

Analog I/O Note: Analog Input Note: RTD Input;Input Channels: 7 (differential);Sensor Type: Pt100, Pt1000, Ni120, Cu100, Cu1000;Wire Connection: 2/3 wire;Resolution: 16-bit;Sampling Rate: 12 sample/second (total);Accuracy: ±0.05% ;Zero Drift: ±0.5 μV/°C;Span Drift: ±20 μV/°C;Common Mode Rejection: 150 dB;Normal Mode Rejection: 100 dB;Input Impedance: >1 MΩ;Open Wire Detection: Yes;Individual Channel Configuration: Yes;3-Wire RTD Lead Resistance Elimination: Yes

Impedance Input: >1 MΩ

Input Type Note: RTD: Pt100, Pt1000, Ni120, Cu100, Cu1000

Electrical Output: N/A

Power Consumption: 2.6 W

Relative Humidity: 10 to 90% RH, non-condensing

Software Settings: • 36 IF-THEN-ELSE Logic Rules: 3 IF conditions with AND or OR operators; 3 THEN actions; 3 ELSE actions • 48 Internal Registers: Hold temporary variables and read/write data via MODBUS/TCP address • 12 Timers: Delay/timing functions • 12 Emails: Send email messages to pre-setemail receivers • 12 CGI Commands: Send pre-set CGI commands • 12 Recipes: Set up THEN/ELSE action groups • 8 P2P Remote Modules: Set up the connection information for the remote OME-WISE-7000 modules • Rule Configuration Website: Access Web server on OME-WISE-7000 controllers to edit and upload logic rules through web browser • MODBUS/TCP Protocol: Real time control and monitoring I/O channels and system status of controllers via SCADA software

Input Voltage Note: Absolute Maximum Input Voltage: Power on: 50 Vdc, Power off 4 Vdc

Data Interface Note: Ethernet Port: 10/100 Base-TX and automatic MDI/MDI-X with PoE (Power over Ethernet);Watchdog: Single;Supported Operating System: MiniOS7;Web HMI: Yes, I/O Pair Connection: Yes

Resistance Elimination: 3-Wire RTD Lead

Storage Temperature, Max: 80 °C

Storage Temperature, Min: -30 °C

Number of Channels, Input: Analog: 7 DIFF

Operating Temperature, Max: 75 °C

Operating Temperature, Min: -25 °C