Alarm: Alarm I/Os: Two contact inputs, TTL 0.5 mA with 10K pull-up; one open collector output 150 mA @ 30 Vdc
Width: 6.13 in
Height: 1.31 in
Length: 4.69 in
Memory: 2 GB SD Flash Card
Weight: 1.08 lb
Display: LCD
Approvals: CE, FCC-B
Hysteresis: ± 1% RH
Input Type: External
Form factor: Wall mount bracket
Memory Note: 8 months of data storage at 1 second recording intervals or 7 years at 10 sec intervals
Probe Style: Industrial Probe
Samples,Max: 85k Samples, Interval 1 sec, 1 Second recording intervals or 7 years at 10 sec intervals
Sensor Type: Probe
Cable Length: 10 ft
Display Note: 32 digits 4.8 x 9.7 mm (0.19 x 0.38")
Probe Length: 5 in
Relay Output: 1.5 A @ 30 Vdc
Accuracy Note: Accuracy/Range at 25°C: Non-Condensing: 10 to 90%: 2.75% RH, 5 to 10% and 90 to 95%: ± 3%, 0 to 5% and 95 to 100%: ± 4%
Configuration: Internal Web UI
Logging Modes: Fixed interval
Non-Linearity: ± 3%
RH Resolution: 0.1%, 12 bit
Repeatability: ± 0.1%
Response Time: Temperature: 5 to 30 sec, RH: 8 sec
Certifications: NIST Traceable Calibration
Data Interface: Ethernet
Probe Diameter: 0.63 in
Supply Current: 0.5 A
Supply Voltage: 9 to 12 Vdc
Measurement Type: Relative Humidity, Temperature
Number of Relays: 2
Supply Power Note: AC Power Adaptor (Included):, Nominal Output: 9 Vdc @ 0.5 A , Back-Up Battery: 9 Vdc, Alkaline (included)
Supply Power Type: DC/Battery
Calibration Option: 5 POINT NIST
Response Time Note: Temperature: 5 to 30 seconds, tau 63%, RH: 8 seconds, tau 63%
Data Interface Note: Ethernet : (RJ45) Fixed or auto negotiating 10/100BASE-T, AUTO MDI/MDIX Protocols: TCP, UDP, SNMP, SMTP, NTP, ARP, ICMP, DHCP, DNS, HTTP, and Telnet
RH Measurement Range: 0 to 100% RH
Temperature Accuracy: ± 0.5 to ± 1.5°C
Battery Size and Type: Alkaline 9V
Electrical Connection: N/A
Cable Temperature, Max: 125 °C
Cable Temperature, Min: -40 °C
Number of Measurements: 2
Temperature Resolution: 0.1 °C
Storage Temperature, Max: 85 °C
Storage Temperature, Min: -40 °C
Temperature Repeatability: ± 0.1 °C
Operating Temperature, Max: 60 °C
Operating Temperature, Min: 0 °C
Relative Humidity Accuracy: ± 2.75% for 10 to 90%; ± 3% for 5 to 10% and 90 to 95%; ± 4% for 0 to 5% and 95 to 100%
Temperature Measurement, Max: 124 °C
Temperature Measurement, Min: -40 °C
Battery Operating Temperature: -18 to 55 °C
AC Adaptor Operating Temperature: 0 to 40 °C